International F5 & F15 Series Service and Installation Manual
For customer service, call (800) 733-8829, (800) 733-8821, Fax (989) 773-3210, www.deleld.com
10
Low pressure cut in at 20 psi.
Low pressure cut out at 5 psi.
Differential setting of 15 psi.
Pressure Control Settings
Display Temperature Control Settings
The display temperature control is located on the evaporator
assembly on the ceiling of the display case. It is field
adjustable and does not require a service agent. The factory
setting is 2.5. Set toward 1 for higher temperatures and
toward 7 for lower temperatures.
Please make small incremental adjustments if
a temperature adjustment is necessary. It may
take an hour or longer to realize the temperature
change depending on the application and location
of the unit.
Contact the service department at Delfield +1
(989) 773-7981 or your local service agent
for additional assistance. Delfield is not
responsible for charges incurred while adjusting
the thermostat.
Base Temperature Control Settings
The base temperature control is located in the machine
compartment. It is field adjustable and does not require a
service agent. The factory setting is 2.5. Set toward 1 for
higher temperatures and toward 7 for lower temperatures.
Please make small incremental adjustments if
a temperature adjustment is necessary. It may
take an hour or longer to realize the temperature
change depending on the application and location
of the unit.
Contact the service department at Delfield +1
(989) 773-7981 or your local service agent
for additional assistance. Delfield is not
responsible for charges incurred while adjusting
the thermostat.